process measurement control display instrumentation products image

Home » Products » Trip amplifiers »

SELECTION GUIDE: Trip amplifiers

Select from: <Single channel> <Dual channel> <Three channel>

PLEASE NOTE with most trip amps, other inputs within the
following ranges can be provided.
Current from 0-1mA to 0-30mA, Voltage from 0-1V to 0-250V.

CURRENT LOOP INTEGRITY FEATURE:
with B12, 107 and 112 type trip amplifiers the current input loop
is maintained when the module is unplugged.

Only the B12-TT and D16-T are microprocessor based.


- - - - - - - - - - - - - - - - - - - - - - - - - - - - -

< Return to Trip Amplifier main page...

Need a panel mount
trip amp solution?
Check out the 500-TT Process Display programmable process display with alarms More details here
Single channel trip amplifiers

TYPE

INPUT

OUTPUT

SET_POINTS

FIELD
RE-RANGE

POWER

MOUNTING

B12-ST Current version
Any true or raised zero signals within the range:
0-20mA
Voltage version
Any true or raised zero signals within the range:
0-5 V
SPCO 'screw driver slot' trim-pot Input

High/Low action
AC 110,200,220,240
~
12, 24, 48VDC
Wall or DIN rail
B12-ST/K Current
0-10mA
0-20mA
4-20mA
Voltage
0-5 V
1-5 V
SPCO Ten-turn precision dial 0-100% High/Low action AC 110,200,220,240
~
12, 24, 48VDC
Wall or DIN rail
COM-2 Any true or raised zero signals within the following ranges:
0-10mA
0-20mA
0-5V
SPCO Single turn dial 0-100% Input type (V/mA)

Span value

High /Low action

Hysteresis
24VDC DIN rail
107-2/2W 4-20mA
10-50mA
SPNO + SPNC Ten-turn precision dial 0-100% High/Low action

Hysteresis
Loop powered Wall or DIN rail
112-2-1 Current
0-10mA
0-20mA
4-20mA
Voltage
0-5 V
1-5 Vspacer for isolator comparison table
DPCOspacer for isolator comparison table Ten-turn precision dials 0-100%
~
Remote set-point optionspacer for isolating signal converter table
High/Low action

Hysteresisspacer for isolator comparison table
AC 110,200,220,240
~
12, 24, 48VDCspacer for isolating signal converter table
Wall or DIN railspacer for isolator comparison table
top of 107 series instrumentation
Dual channel trip amplifiers

TYPE

INPUT

OUTPUT

SET_POINTS

FIELD
RE-RANGE

POWER

MOUNTING

B12-DT Current version
Any true or raised zero signals within the range:
0-20mA
Voltage version
Any true or raised zero signals within the range:
0-5 V
2x SPCO 'screw driver slot' trim-pots Input

High/Low action

Interlock function
AC 110,200,220,240
~
12, 24, 48VDC
Wall or DIN rail
B12-DT/K Current
0-10mA
0-20mA
4-20mA
Voltage
0-5 V
1-5 V
etc
2x SPCO Ten-turn precision dials 0-100% High/Low action

Interlock function
AC 110,200,220,240
~
12, 24, 48VDC
Wall or DIN rail
112-2A-2 Current
0-10mA
0-20mA
4-20mA
Voltage
0-5 V
1-5 V
Note:
Optional second inputspacer for isolator comparison table
SPCO + SP
per channelspacer for isolator comparison table
Ten-turn precision dials 0-100%spacer for isolating signal converter table High/Low action

Interlock function

Hysteresisspacer for isolator comparison table
AC 110,200,220,240
~
12, 24, 48VDCspacer for isolating signal converter table
Wall or DIN railspacer for isolator comparison table
D16-T Universal
PRT
T/C
mA
mV
SPCO per channel Configuration software PC 24VDC DIN rail
Three channel trip amplfier

TYPE

INPUT

OUTPUT

MAIN FEATURES

FIELD
RE-RANGE

POWER

MOUNTING

B12-TTspacer for isolator comparison table Current
0-10mA
0-20mA
4-20mA
Voltage
0-10 V
0-5 V
spacer for isolator comparison table
3x SPspacer for isolator comparison table Monitored channel status indication
~
4-digit display of monitored variable
~
Programmable set-points (digital precision)
~
Scaling 0-100%, V, mA or custom engineering units
~
10 break-point user linearisationspacer for isolating signal converter table
13 functions set via front panel keypad and four digit LED display. See trip amplifier data sheet.
spacer for isolator comparison table
Universal
85-260VAC
~
11-30VDC
(12-24VAC)
spacer for isolating signal converter table
Wall or DIN railspacer for isolator comparison table
The above functions are also available in the 500-TT Process Display (digital panel meter)
top of 107 series instrumentation